ACT Integrated Systems has completed the fabrication and installation of two custom air handling units for Johanna Foods, Flemington NJ. These units were installed in the fall of 2020. Johanna has recently released three additional units for installation in the 3rd and 4th quarters of 2021.
Unit construction included:
- Sectional construction with extruded aluminum mating flanges.
- Base: Structural steel base with lifting lugs.
- Floors: Foam injected R-20.
- Walking surface: welded stainless steel tread plate walking surface with 2” turned upside walls and
dedicated 1 ½” capped floor drains. - Casing: 3” thick, foam-injected, R-20, 100% thermal break casings with 18 g stainless steel interior
liners and .060” embossed aluminum exterior. - Roof: EPDM
- Fans: Direct drive plenum type with factory mounted VFDs.
- Mixing: Full economizer with minimum/maximum O/A dampers, relief and return dampers with stainless steel construction.
- Heating: Steam distributing.
- Cooling: DX Ammonia
- Filtration: MERV-13 pre-filters and 99.97% high-capacity blow thru HEPA.

Left side of units

Right side of units

Mixing/economizer section

Direct drive fans

Extruded aluminum mating flanges

Blow thru HEPA filter sections

Fan inlet isolation dampers

Air Blenders


For design assistance it more information, contact us at 703-547-1680 or on the web at www.aircleaningtechnologies.com